FO Universal wbGGFR Safety / U-DQ(ZN)BH Safety cable E30 metal-free, water resistant, rodent protection, in accordance with IEC 60332.1 and IEC 60332.3 C 30 minutes System Circuit Integrity according to DIN 4102-12

Fibre optic cables and panels
Manufacturer — Datwyler
Description
Metal-free fibre optic safety cable with multiple loose tubes, up to 60 fibres.
The optimal combination of flame retardant fibre coating and flame-inhibiting stabilizing elements ensures enhanced functional integrity (System Circuit Integrity) in case of fire for 30 minutes (transmission of audio, video and 1Gbit/s signals approved by a certified test report).

Application
Safety applications in tunnels, underground railways, banks, insurance companies, large-scale industry.
LAN backbone.
Indoor and outdoor cabling.
Can be installed in cable platforms, trays, ducts and vertical shafts.
Can be spliced in FO distributors.

Mechanical properties
Temperature range storage: -25 / +70°C IEC 60794-1-2 F1
during installation: -10 / +50°C
in operation: -25 / +60°C
Tensile performance: IEC 60794-1-2 E1
Crush resistance: IEC 60794-1-2 E3
Repeated bending: IEC 60794-1-2 E6
Torsion: IEC 60794-1-2 E7
Bend: IEC 60794-1-2 E11
Water penetration: IEC 60794-1-2 F5

Optical properties
The cables are available with different types of optical fibre (see fibre data sheets).

Standards
Imprint
DATWYLER «cable type» «Datwyler designation» «DIN designation» «no. of fibres» «fibre type» «add. text» «batch no.» «meter marks»
Zero halogen, no corrosive gases
IEC 60754-1/-2, EN 50267-2-1/-2-2, VDE 0482-267-2-1/-2-2
Flame propagation
IEC 60332-1/-2, EN 60332-1-2, VDE 0482-332-1-2
Flame spread
IEC 60332.3 C, EN 50266-2-4, VDE 0482-266-2-4
Smoke density
IEC 61034-1/-2, EN 61034-1/-2 (EN 50268-1/-2), VDE 0482-1034-1/-2 (VDE 0482-268-1/-2)
Circuit Integrity (FE180)
IEC 60331-11, IEC 60331-25, VDE 0472 part 814, EN 50200 PH 90, EN 50362, VDE 0482-200, VDE 0482-362
System circuit integrity
according to DIN 4102 part 12, VKF Fire Safety Application No. 24176